SINAMICS V20 1AC 200-240V -15/+10% 47-63Hz 3kW with 150% overload for 60s integrated Filter C1 I/O: 4 DI, 2 DQ, 2AI, 1AO Fieldbus: USS/Modbus with built-in BOP protection IP20/UL open Type Size:AD 136x176.5x160(WxHxD)
| |
Width: | 136.600 mm |
Height: | 176.500 mm |
Depth: | 158.800 mm |
Number of digital inputs: | 4.000 |
Number of analogue inputs: | 2.000 |
Number of analogue outputs: | 1.000 |
Supporting protocol for LON: | false |
Number of HW-interfaces industrial Ethernet: | 0.000 |
Number of HW-interfaces RS-232: | 1.000 |
Number of HW-interfaces RS-422: | 0.000 |
Number of HW-interfaces RS-485: | 1.000 |
Number of HW-interfaces serial TTY: | 0.000 |
Number of HW-interfaces USB: | 0.000 |
Number of HW-interfaces parallel: | 0.000 |
Number of HW-interfaces other: | 1.000 |
With optical interface: | false |
Supporting protocol for TCP/IP: | false |
Supporting protocol for ASI: | false |
Supporting protocol for PROFIBUS: | false |
Supporting protocol for CAN: | false |
Supporting protocol for INTERBUS: | false |
Supporting protocol for KNX: | false |
Supporting protocol for Modbus: | true |
Supporting protocol for Data-Highway: | false |
Supporting protocol for DeviceNet: | false |
Supporting protocol for SUCONET: | false |
Supporting protocol for other bus systems: | true |
Degree of protection (IP): | IP20 |
With PC connection: | false |
Supporting protocol for SERCOS: | false |
Supporting protocol for INTERBUS-Safety: | false |
Mains voltage: | 200.000 V | 240.000 V |
4-quadrant operation possible: | false |
Number of interfaces PROFINET: | 0.000 |
Type of converter: | U converter |
Number of phases output: | 3 |
Number of phases input: | 1 |
Integrated breaking resistance: | false |
Application in industrial area permitted: | true |
Application in domestic- and commercial area permitted: | true |
Max. output frequency: | 550.000 Hz |
Max. output at linear load at rated output voltage: | 3.000 kW |
Max. output at quadratic load at rated output voltage: | 3.000 kW |
Relative symmetric net voltage tolerance: | 10.000 % |
Relative symmetric net frequency tolerance: | 5.000 % |
Supporting protocol for AS-Interface Safety at Work: | false |
Supporting protocol for DeviceNet Safety: | false |
Supporting protocol for EtherNet/IP: | false |
Supporting protocol for Foundation Fieldbus: | false |
Supporting protocol for PROFINET CBA: | false |
Supporting protocol for PROFINET IO: | false |
Supporting protocol for PROFIsafe: | false |
Supporting protocol for SafetyBUS p: | false |
Max. output voltage: | 240.000 V |
Nominal output current I2N: | 13.600 A |