Mounting method: | DIN rail (top hat rail) 35 mm |
With remote signalling contact: | false |
Number of conductors (without earthing): | 3.000 |
Construction size: | 3 modular spacing |
Voltage protection level: | 1.250 kV |
Max. continuous voltage AC: | 275.000 V |
Nominal discharge surge current (8/20): | 20.000 kA |
Nominal voltage AC: | 230.000 V |
Category type 2: | true |
Voltage protection level L-N: | 1.250 kV |
Signalling at the device: | Optic |
Max. continuous voltage DC: | 350.000 V |
Degree of protection (IP): | IP20 |
Voltage protection level N-PE: | 1.250 kV |
Integrated backup fuse: | false |
Max. conductor cross section solid (solid, stranded): | 25.000 mm² |
Max. conductor cross section flexible (fine-strand): | 16.000 mm² |
System configuration DC: | false |
System configuration IT: | false |
System configuration TN: | true |
System configuration TN-C: | true |
System configuration TN-S: | false |
System configuration TT: | false |
System configuration other: | false |
System configuration TN-C-S: | false |
Max. discharge surge current (8/20): | 120.000 kA |
Short-circuit breaking capacity (Isccr): | 100.000 kA |
Max. overcurrent protection device, series connection (fuse): | 125.000 A |
Integrated short-circuit protection: | false |
Integrated short-circuit protection selective to fuse gG: | 125.000 A |
Leakage-current free: | false |